4-16

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Sets the voltage boost level for starting and acceleration when Custom V/Hz mode is
selected in Torque Perf Mode (53).

Sets the boost level for steady state or deceleration when Fan/Pmp V/Hz or Custom
V/Hz modes are selected in Torque Perf Mode (53).

Sets the voltage the drive will output at Break Frequency (72).

Sets the frequency the drive will output at Break Voltage (71).

Sets the method of speed regulation.

69

Start/Acc Boost

Range:

0.0 to Motor NP Volts x 0.25 [0.1 VAC]

Default:

Based on drive rating

Access:

1

Path: Motor Control>Volts per Hertz

See also:

53, 70, 83

70

Run Boost

Range:

0.0 to Motor NP Volts x 0.25 [0.1 VAC]

Default:

Based on drive rating

Access:

1

Path: Motor Control>Volts per Hertz

See also:

53, 69, 83

71

Break Voltage

Range:

0.0 to Motor NP Volts [0.1 VAC]

Default:

Motor NP Volts x 0.25

Access:

1

Path: Motor Control>Volts per Hertz

See also:

53, 72, 83

72

Break Frequency

Range:

0.0 to 250.0 [0.1 Hz]

Default:

Motor NP Freq x 0.25

Access:

1

Path: Motor Control>Volts per Hertz

See also:

53, 71, 83

80

Speed Mode

Range:

0 = Open Loop
1 = Slip Comp
2 = Process PI

Default:

0 = Open Loop

Access:

1

Path: Speed Command>Spd Mode & Limits

See also:

124 -138