Parameter Descriptions

4-65

Adapter that has requested exclusive control of drive logic functions.

If an adapter is in local lockout, all other functions (except stop) on all other modules
are locked out and non-functional. Local control can be obtained only when the drive
is stopped.

Parameter number whose value will be written from a communications device data
table.

Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type will disable the link

Refer to the appropriate communications option board manual for datalink information.

Parameter number whose value will be written from a communications device data
table.

Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type will disable the link.

Refer to the appropriate communications option board manual for datalink information.

297

Local Owner

Range:

See Stop Owner (288)

Default:

Read Only

Access:

1

Path: Communication>Masks & Owners

See also:

276 - 285

300
301

Data In A1 - Link A Word 1
Data In A2 - Link A Word 2

Range:

0 to 387 [1]

Default:

0 (Disabled)

Access:

1

Path: Communication>Datalinks

See also:

302
303

Data In B1 - Link B Word 1
Data In B2 - Link B Word 2

Range:

0 to 387 [1]

Default:

0 (Disabled)

Access:

1

Path: Communication>Datalinks

See also: