Parameter Descriptions

4-13

Enables/disables the compensation correction options.

Bit 0 - Reflect Wave

Enables/disables reflected wave correction software, which reduces overvoltage
transients from the drive to the motor. For lead lenghts beyond 300 feet, enable this
feature.

Bit 1 - Enable Jerk

Enables/disables the jerk limit in the current limiter that helps to eliminate
overcurrent trips on fast accelerations. Disable this feature if your application
requires the actual acceleration of the motor to be faster than .25 sec.

Manual (0): Flux is established for Flux Up Time (58) before acceleration

Auto (1): Flux is established for a calculated time period based on motor nameplate
data. Flux Up Time (58) is not used.

56

Compensation

Range:

See figure 4.5

Default:

See figure 4.5

Access:

1

Path: Motor Control>Torq Attributes

See also:

Figure 4.5 – Compensation (56)

1

0

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Reflect W

av

e

Enab

le Jer

k

Ixo A

utoCalc

Nibble 1

Nibble 2

Nibble 3

Nibble 4

57

Flux Up Mode

Range:

0 = Manual
1 = Automatic

Default:

0 = Manual

Access:

1

Path: Motor Control>Torq Attributes

See also:

53, 58