324 analog in 1 loss, 325 analog in 2 hi, 326 analog in 2 lo – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual

Page 102

Advertising
background image

4-70

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Selects drive response when an analog signal loss is detected. (1.6V = signal loss,
1.9V = end of signal loss; 3.2 mA = signal loss, 3.8 mA = end of signal loss.)

One of the selections (1=Fault) stops the drive on signal loss. All other choices make it
possible for the input signal to return to a usable level while the drive is still running.

Important: Note that there is no signal loss detection while the input is in bipolar

voltage mode.

Sets the highest 10 value to the analog input 2 scaling block.

Sets the lowest input value to the analog input 2 scaling block.

324

Analog In 1 Loss

Range:

0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency
command)
4 = Set Input Hi (use Maximum Speed as frequency
command)
5 = Goto Preset1 (use Preset 1 as frequency
command)
6 = Hold OutFreq (maintain last output frequency)

Default:

0 = Disabled

Access:

1

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

!

ATTENTION: Setting parameter 324 to a value greater than 1 allows the
input signal to return to a usable level while the drive is running. If a lost
analog signal is restored while the drive is running, the drive will ramp to
the restored reference level at the rate specified in Accel Time 1 (140),
Accel Time 2 (141), Decel Time 1 (142), and Decel Time 2 (143). Be
aware that an abrupt speed change may occur depending upon the new
reference level and the rate specified in these parameters. Failure to
observe this precaution could result in bodily injury.

325

Analog In 2 Hi

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.1 V]
0.0 to 10.000 V [0.1 V]

Default:

10 V

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

326

Analog In 2 Lo

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.1 V]
0.0 to 10.000 V [0.1 V]

Default:

0.000 V

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92