Troubleshooting the Drive

5-5

Drive OL
Level 2

The calculated IGBT temperature requires a reduction in Current Limit.
If Drive OL Mode (150) is disabled and the load is not reduced, an
overload fault will eventually occur.

Flux
Amps Ref
Rang

Result of autotune procedure (61).

IntDBRes
OvrHeat

The drive has temporarily disabled the dynamic braking regulator
because the resistor temperature has exceeded a predetermined
value.

IR Volts
Range

The drive autotuning default is Calculate and the value calculated for IR
Drop Volts is not in the range of acceptable values. This alarm should
clear when all motor nameplate data is properly entered.

MaxFreq
Conflict

The sum of Maximum Speed (82) and Overspeed Limit (83) exceeds
Maximum Freq (55). Raise Maximum Freq (55) or lower Maximum
Speed (82) and/or Overspeed Limit (83) so that the sum is less than or
equal to Maximum Freq (55).

Motor
Type Cflct

Motor Type (90) has been set to Sync Prm Mag or Sync Reluc, and one
or more DC functions (for example, DC Boost, DC Brake, etc.) have
been activated. DC injection functions are imcompatible with
synchronous motors and may demagnetize them.

NP Hz
Conflict

Fan/pump mode is selected in Torq Perf Mode (53), and the ratio of
Motor NP Hertz (43) to Maximum Freq (55) is greater than 26.

Power
Loss

Drive has sensed a power line loss.

Prechrg
Actv

Drive is in the initial DC bus precharge state.

Speed
Ref Cflct

Speed Ref x Sel or PI Reference Sel is set to “Reserved”.

Under-
Voltage

The bus voltage has dropped below a predetermined value.

VHz Neg
Slope

Custom V/Hz mode has been selected in Torq Perf Mode (53) and the
V/Hz slope is negative.

Table 5.4 – Alarm Names Cross-Referenced by Alarm Numbers

No.

1

1

Alarm numbers not listed are reserved for future use.

Alarm

No.

1

Alarm

1

Precharge Active

20

Bipolar Conflict

2

UnderVoltage

21

Motor Type Conflict

3

Power Loss

22

NP Hz Conflict

5

Analog In Loss

23

MaxFreq Conflict

6

IntDBRes OvrHeat

24

VHz Neg Slope

8

Drive OL Level 1

25

IR Volts Range

9

Drive OL Level 2

26

FluxAmps Ref Rang

17

Dig In ConflictA

27

Speed Ref Cflct

18

Dig In ConflictB

30

DigIn Bad Value

19

Dig In ConflictC

Table 5.3 – Alarm Descriptions (Continued)

Alarm

Ty

p

e

Description