5-14

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

5.5

Test Point Codes and Functions

Table 5.7 – Fault Names Cross-Referenced by Fault Number

No.

1

1

Fault numbers not listed are reserved for future use.

Fault

No.

1

Fault

No

1

Fault

2

Function Loss

38

Phase U to Grnd

80

AutoTune Aborted

3

Power Loss

39

Phase V to Grnd

81-
86

Port 1-6 DPI Loss

4

UnderVoltage

40

Phase W to Grnd

100 Parameter Chksum

5

OverVoltage

41

Phase UV Short

101 UserSet1 Chksum

7

Motor Overload

42

Phase VW Short

102 UserSet2 Chksum

8

Heatsink OvrTemp

43

Phase UW Short

103 UserSet3 Chksum

9

Trnsistr OvrTemp

48

Params Defaulted

104 Pwr Brd Chksum1

12

HW OverCurrent

63

Shear Pin

105 Pwr Brd Chksum2

13

Ground Fault

64

Drive Overload

106 Incompat MCB-PB

24

Decel Inhibit

69

DB Resistance

107 Replaced MCB-PB

25

OverSpeed Limit

70

Power Unit

108 Anlg Cal Chksum

29

Analog In Loss

71-76 Port 1-6 Net Loss

120 I/O Board Mismatch

33

Auto Rstrt Tries

77

IR Volts Range

121 I/O Board Comm

Loss

36

SW OverCurrent

78

FluxAmpsRef Rang

122 I/O Board Fail

37

Phase Imbalance

79

Excessive Load

207 Gate Kill

Table 5.8 – Test Point Codes and Functions

Code Selected in Testpoint x

Sel (234, 236)

Function Whose Value is Displayed in

Testpoint x Data (235, 237)

1

DPI Error Status

2

Heatsink Temperature

3

Active Current Limit

4

Active PWM Frequency

5

Lifetime MegaWatt Hours

1

1

Use the equatio

n

below to calculate total Lifetime MegaWatt Hours.

6

Lifetime Run Time

7

Lifetime Powered Up Time

8

Lifetime Power Cycles

9

Life MegaWatt Hours Fraction

(1)

10

Life MegaWatt Hours Fraction Units

(1)

11-99

Reserved for Factory Use

Value of Code 9

Value of Code 10

------------------------------------------

0.1

×

Value of Code 5

+

Total Lifetime Megawatt Hours

=