195 mop rate, 196 param access lvl, 197 reset to defalts – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 75

Parameter Descriptions
4-43
Sets the rate of change of the MOP reference in response to a digital input.
Displays the present parameter access level. Refer to chapter 3 for more information
about parameter access levels.
Resets all parameter values to defaults. Option 1 resets the drive to factory settings.
Options 2 and 3 resets the drive to alternate voltage and current rating.
Figure 4.12 – Save MOP Ref (194)
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Save
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At P
owr Do
wn
At Stop
Nibble 1
Nibble 2
Nibble 3
Nibble 4
195
MOP Rate
Range:
0.2 to 250.0 [0.1 Hz/sec]
Default:
1.0 Hz/sec
Access:
1
Path: Utility>MOP Config
See also:
196
Param Access Lvl
Range:
0 = Basic
1 = Advanced
Default:
Read Only
Access:
0
Path: Utility>Drive Memory
See also:
197
Reset To Defalts
Range:
0 = Ready
1 = Factory
2 = Low Voltage
3 = High Voltage
Default:
0 = Ready
Access:
0
Path: Utility>Drive Memory
See also: