Parameter Descriptions

4-35

Sets the responsiveness of the bus regulator.

Sets the method and sequence of the DC bus regulator voltage. Choices are dynamic
brake, frequency adjust, or both.

Sequence is determined by programming or digital input to the terminal block.

If a dynamic brake resistor is connected to the drive, Bus Reg Mode A and Bus Reg
Mode B must be set to option 2, 3, or 4.

160

Bus Reg Gain

Range:

0 to 5000 [1]

Default:

450

Access:

1

Path: Dynamic Control>Stop/Brake Modes

See also:

161, 162

161
162

Bus Reg Mode A
Bus Reg Mode B

Range:

0 = Disabled
1 = Adjust Freq
2 = Dynamic Brak
3 = Both - DB 1st
4 = Both - Frq 1st

Default:

Mode A: 0 = Disabled
Mode B: 0 = Disabled

Access:

0

Path: Dynamic Control>Stop/Brake Modes

See also:

160, 163, 361-366