62 ir voltage drop, 63 flux current ref, 64 ixo voltage drop – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual

Page 47

Advertising
background image

Parameter Descriptions

4-15

Important: Rotate Tune (2) is used when motor is uncoupled from the load. Results

may not be valid if a load is coupled to the motor during this procedure.

Calculate (3) = This setting uses motor nameplate data to automatically set IR
Voltage Drop and Flux Current Ref.

Value of volts dropped across the resistance of the motor stator. Used only when
Torque Perf Mode (53) is set to Sensrls Vect or SV Economize.

Value of amps for full motor flux. Used only when Torque Perf Mode (53) is set to
Sensrls Vect or SV Economize.

Sets the value of the voltage drop due to leakage inductance of the motor. Used only
when Torque Perf Mode (53) is set to Sensrls Vect or SV Economize.

!

ATTENTION: Rotation of the motor in an undesired direction can occur
during this procedure (Autotune (61) = Rotate Tune (2)). To guard against
possible injury and/or equipment damage, it is recommended that the
motor be disconnected from the load before proceeding.

62

IR Voltage Drop

Range:

0.0 to Motor NP Volts x 0.25 [0.1 VAC]

Default:

Motor NP Volts x 0.25

Access:

1

Path: Motor Control>Torq Attributes

See also:

53

63

Flux Current Ref

Range:

0.00 to Motor NP FLA [0.01 Amps]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Torq Attributes

See also:

53

32

64

Ixo Voltage Drop

Range:

0.00 to 230.0 or 460.0 V [0.1 VAC]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Torq Attributes

See also:

Advertising