Parameter Descriptions

4-81

Sets the on delay time for the digital outputs. This is the time between the occurrence
of a condition and activation of the relay.

Sets the off delay time for the digital outputs. This is the time between the
disappearance of a condition and de-activation of the relay.

Selects the drive status that will energize an output relay.

382

Dig Out1 OnTime

Range:

0.00 to 600.00 sec [0.01 sec]

Default:

0.00 sec

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also:

380

383

Dig Out1 OffTime

Range:

0.00 to 600.00 sec [0.01 sec]

Default:

0.00 sec

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also:

380

384

Digital Out2 Sel

Range:

1 = Fault
2 = Alarm
3 = Ready
4 = Run
5 = Forward Run
6 = Reverse Run
7 = Auto Restart
8 = Powerup Run
9 = At Speed
10 = At Freq
11 = At Current
12 = At Torque
13 = At Temp
14 = At Bus Volts
15 = At PI Error
16 = DC Braking
17 = Curr Limit
18 = Economize
19 = Motor Overld
20 = Power Loss
21 = Input 1 Link
22 = Input 2 Link
23 = Input 3 Link
24 = Input 4 Link
25 = Input 5 Link
26 = Input 6 Link
27 = Shunt Trip
28 = Aux Run

Default:

4 = Run

Access:

0

Path: Inputs & Output>Digital Outputs

See also:

1 - 4, 12, 48, 53, 137, 147, 157, 184, 218, 381-383, 385, 386