LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Refer to section 5.8.1 for information on accessing the fault queue using the LCD OIM.
Refer to instruction manual D2-3488 for information on accessing the fault queue
using VS Utilities software.

5.4.2 Clearing Faults

A fault condition can be cleared by the following:

Step 1. Press

or any F-Key to acknowledge the fault and remove the fault

pop-up from the LCD OIM screen.

Step 2. Address the condition that caused the fault. The cause must be corrected

before the fault can be cleared.

Step 3. After corrective action has been taken, clear the fault using one of the

following:

Setting Fault Clear (240) to Clear Faults (1).

Press F1 (Cflt) from the fault queue screen.

Issuing a Stop-Clear Faults command from the control source.

Resetting faults will clear the faulted status indication. If any fault condition still exists,
the fault will be latched, and another entry made in the fault queue.

Note that performing a fault reset does not clear the fault queue. Clearing the fault
queue is a separate action. See the Fault Clear (240) parameter description.