LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Selects whether the signed value or absolute value of a parameter is used before
being scaled to drive the analog output.
Selects the source of the value that drives the analog output.
341
Anlg Out Absolut
Range:
See figure 4.32
Default:
See figure 4.32
Access:
1
Path: Inputs & Outputs>Analog Outputs
See also:
342
Figure 4.32 – Anlg Out Absolute (341)
x
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0 =Disabled
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1
Nibble 1
Nibble 2
Nibble 3
Nibble 4
342
Analog Out1 Sel
Range:
0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = Application
Default:
0 = Output Freq
Access:
0
Path: Inputs & Outputs>Analog Outputs
See also:
1 - 7, 12, 135 - 138, 219, 220