Troubleshooting the Drive

5-13

UnderVoltage

4


DC bus voltage fell below the
minimum value of 407V DC at
400/480V input or 204V DC at
200/240V input.

Enable/disable with Fault
Config 1(233).

Monitor the incoming AC line
for low voltage or power
interruption.

UserSet1
Chksum

101

The checksum read from the
user set does not match the
checksum calculated.

Re-save user set.

UserSet2
Chksum

102

UserSet3
Chksum

103

Table 5.6 – Fault Descriptions and Corrective Actions (Continued)

Fault

No.

Ty

p

e

Description

Action