Parameter Descriptions

4-17

Sets the low limit for the speed reference after scaling is applied.

Sets the high limit for the speed reference after scaling is applied.

81

Minimum Speed

Range:

0.0 to Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

0

Path: Speed Command>Spd Mode & Limits

See also:

83, 92, 95

!

ATTENTION: The drive can operate at and maintain zero speed. The
user is responsible for assuring safe conditions for operating personnel
by providing suitable guards, audible or visual alarms, or other devices
to indicate that the drive is operating or may operate at or near zero
speed. Failure to observe this precaution could result in severe bodily
injury or loss of life.

82

Maximum Speed

Range:

5.0 to 400.0 [0.1 Hz]

Default:

60.0 Hz

Access:

0

Path: Speed Command>Spd Mode & Limits

See also:

55, 83, 91, 94, 202

!

ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of safe
operation at the maximum operating speed of the drive. Overspeed
detection in the drive determines when the drive shuts down.

See figure

4.6

. Failure to observe this precaution could result in bodily injury.