Parameter Descriptions

4-59

Sets the baud rate for attached drive peripherals. When changing this value, the drive
must be reset for the change to take effect

The final logic command to the drive resulting from the combination of all port
requests and masking functions. Each bit or set of bits represent a command to the
drive or follower device. For LiquiFlo 1.5 drives, bit 6 will always = 0.

270

DPI Baud Rate

Range:

0 = 125 kbps
1 = 500 kbps

Default:

1

Access:

1

Path: Communication>Comm Control

See also:

271

Drive Logic Rslt

Range:

See figure 4.26

Default:

Read Only

Access:

1

Path: Communication>Comm Control

See also:

Figure 4.26 – Drive Logic Rslt (271)

0

1

1

0

0

0

0

1

0

1

1

1

0

0

0

0

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition Active
0 =Condition Inactive
x =Reserved

Bit #

Stop

Star

t

Jog

Clear F

ault

Forw

ard

Re

verse

Local Contr

l

Mop Inc

Accel 1

Accel 2

Decel 1

Decel 2

Spd Ref ID 0

(1)

Spd Ref ID 1

(1)

Spd Ref ID 2

(1)

MOP Dec

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Bits

(1)

Description

14

13

12

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

No Command - Man.
Mode
Ref A Auto
Preset 2 Auto
Preset 3 Auto
Preset 4 Auto
Preset 5 Auto
Preset 6 Auto
Preset 7 Auto