47 motor ol hertz, 48 motor overload amps, 49 imbalance limit – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 43: 50 imbalance time

Parameter Descriptions
4-11
Selects the output frequency below which the motor operating current is derated. The
motor thermal overload will generate a fault at lower levels of current. For all settings
of overload Hz other than zero, the overload capacity is reduced to 70% when output
frequency is zero.
Sets the amps threshold for motor overload fault.
Motor FLA x OL Factor = Operating Level
Sets the fault threshold for motor current imbalance.
Sets the time delay in generating a motor current imbalance fault.
47
Motor OL Hertz
Range:
0.0 to Motor NP Hz [0.1 Hz]
Default:
0
Access:
0
Path: Motor Control>Motor Data
See also:
42, 220
48
Motor Overload Amps
Range:
1.0 to 2000.0 [0.1 A]
Default:
Based on Drive Type
Access:
1
Path: Motor Control>Motor Data
See also:
49
Imbalance Limit
Range:
0.0 to 40.0 [0.1 %]
Default:
10.0
Access:
1
Path: Motor Control>Motor Data
See also:
50, 221
50
Imbalance Time
Range:
1.0 to 10.0 [0.1 sec]
Default:
5.0
Access:
1
Path: Motor Control>Motor Data
See also:
49, 221