47 motor ol hertz, 48 motor overload amps, 49 imbalance limit – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual

Page 43: 50 imbalance time

Advertising
background image

Parameter Descriptions

4-11

Selects the output frequency below which the motor operating current is derated. The
motor thermal overload will generate a fault at lower levels of current. For all settings
of overload Hz other than zero, the overload capacity is reduced to 70% when output
frequency is zero.

Sets the amps threshold for motor overload fault.

Motor FLA x OL Factor = Operating Level

Sets the fault threshold for motor current imbalance.

Sets the time delay in generating a motor current imbalance fault.

47

Motor OL Hertz

Range:

0.0 to Motor NP Hz [0.1 Hz]

Default:

0

Access:

0

Path: Motor Control>Motor Data

See also:

42, 220

48

Motor Overload Amps

Range:

1.0 to 2000.0 [0.1 A]

Default:

Based on Drive Type

Access:

1

Path: Motor Control>Motor Data

See also:

49

Imbalance Limit

Range:

0.0 to 40.0 [0.1 %]

Default:

10.0

Access:

1

Path: Motor Control>Motor Data

See also:

50, 221

50

Imbalance Time

Range:

1.0 to 10.0 [0.1 sec]

Default:

5.0

Access:

1

Path: Motor Control>Motor Data

See also:

49, 221