LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Displays the source that initiated the most recent stop sequence. It will be cleared (set
to 0) during the next start sequence.

Current state of the digital inputs on the terminal block.

Current state of the digital outputs.

215

Last Stop Source

Range:

0 = Pwr Removed
1 = Network
2 = DPI Port 2
3 = DPI Port 3
4 = DPI Port 4
5 = DPI Port 5
6 = Reserved
7 = Digital In
8 = Fault
9 = Not Enabled
10 = Sleep
11 = Jog

Default:

Read Only

Access:

1

Path: Utility>Diagnostics

See also:

216

Dig In Status

Range:

See figure 4.18

Default:

Read Only

Access:

1

Path: Utility>Diagnostics
Inputs & Outputs>Digital Inputs

See also: 361-366

Figure 4.18 – Dig In Status (216)

0

0

0

0

0

0

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Input Present
0 =Input Not Present
x =Reserved

Bit #

Digital In1

Digital In2

Digital In3

Digital In4

Digital In5

Digital In6

Nibble 1

Nibble 2

Nibble 3

Nibble 4

217

Dig Out Status

Range:

See figure 4.19

Default:

Read Only

Access:

1

Path: Utility>Diagnostics
Inputs & Outputs>Digital Outputs

See also:

380-384