LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Displays the source that initiated the most recent stop sequence. It will be cleared (set
to 0) during the next start sequence.
Current state of the digital inputs on the terminal block.
Current state of the digital outputs.
215
Last Stop Source
Range:
0 = Pwr Removed
1 = Network
2 = DPI Port 2
3 = DPI Port 3
4 = DPI Port 4
5 = DPI Port 5
6 = Reserved
7 = Digital In
8 = Fault
9 = Not Enabled
10 = Sleep
11 = Jog
Default:
Read Only
Access:
1
Path: Utility>Diagnostics
See also:
216
Dig In Status
Range:
See figure 4.18
Default:
Read Only
Access:
1
Path: Utility>Diagnostics
Inputs & Outputs>Digital Inputs
See also: 361-366
Figure 4.18 – Dig In Status (216)
0
0
0
0
0
0
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Input Present
0 =Input Not Present
x =Reserved
Bit #
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
Nibble 1
Nibble 2
Nibble 3
Nibble 4
217
Dig Out Status
Range:
See figure 4.19
Default:
Read Only
Access:
1
Path: Utility>Diagnostics
Inputs & Outputs>Digital Outputs
See also:
380-384