91 speed ref a hi, 92 speed ref a lo, 93 speed ref b sel – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 52

4-20
LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Scales the upper value of the Speed Ref A Sel (90) selection when the source is an
analog input.
Scales the lower value of the Speed Ref A Sel (90) selection when the source is an
analog input.
Selects the source of the speed reference to the drive unless Preset Speed 1-7
(101-107)
is selected.
Note that the manual reference command and input OIM Control can override the
reference control source.
91
Speed Ref A Hi
Range:
-/+Maximum Speed [0.1 Hz]
Default:
Maximum Speed
Access:
0
Path: Speed Command>Speed References
See also:
82
92
Speed Ref A Lo
Range:
-/+Maximum Speed [0.1 Hz]
Default:
0.0 Hz
Access:
0
Path: Speed Command>Speed References
See also: 81
93
Speed Ref B Sel
Range:
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Network
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
23 = Reserved
Default:
17 = Preset Spd 7
Access:
0
Path: Speed Command>Speed References
Speed Command>Control Src Select
See also:
2, 91-93, 101-107, 117-120, 192-194, 213, 272, 273, 361-366