4-24
LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Scales the upper value of the Trim In Select (117) selection when the source is an
analog input.
Scales the lower value of the Trim In Select (117) selection when the source is an
analog input.
Important: Parameters in the Slip Comp Group (121-123) are used to enable and
tune the slip compensation regulator. To allow the slip compensation
regulator to control drive operation, Speed Mode (80) must be set to 1
(Slip Comp).
Sets the amount of compensation to drive output at motor FLA. If parameter 61
(Autotune) = 3 (Calculate), changes made to this parameter will not be accepted.
Figure 4.7 – Trim Out Select (118)
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Trimmed
0 =Not Trimmed
x =Reserved
Bit #
Factory Default Bit Values
Tr
im Ref A
Tr
im Ref B
Nibble 1
Nibble 2
Nibble 3
Nibble 4
119
Trim Hi
Range:
-/+Maximum Speed [0.1 Hz]
Default:
60.0 Hz
Access:
1
Path: Speed Command>Speed Trim
See also:
82, 117
120
Trim Lo
Range:
-/+Maximum Speed [0.1 Hz]
Default:
0.0 Hz
Access:
1
Path: Speed Command>Speed Trim
See also: 117
121
Slip RPM @ FLA
Range:
0.0 to 1200.0 RPM
Default:
Based on Motor NP RPM
Access:
1
Path: Speed Command>Slip Comp
See also:
61, 80, 122, 123