Parameter Descriptions

4-41

Sets the time that the drive will remain in power loss mode before a fault is issued.

Sets the level at which the Power Loss Mode selection will occur.

Selects the source for control of drive direction.

Unipolar = Drive receives unsigned reference (0 to 32767) and direction command
separately (from the DPI port). For example, the direction keys on an OIM apply the
direction to the reference.

Bipolar = Drive receives signed reference (-32767 to 32767). In this case, the
direction keys have no effect.

Reverse Disable = Drive receives signed reference (-32767 to 32767); however,
regardless of the reference, the drive is not permitted to reverse.

185

Power Loss Time

Range:

0.0 to 60.0 sec [0.1 sec]

Default:

0.5 sec

Access:

0

Path: Dynamic Control>Power Loss

See also:

184

186

Power Loss Level

Range:

0.0 to 99.9 [0.1 VDC]

Default:

Drive Rated Volts

Access:

1

Path: Dynamic Control>Power Loss

See also:

184

190

Direction Mode

Range:

0 = Unipolar
1 = Bipolar
2 = Reverse Dis

Default:

2 = Reverse Dis

Access:

0

Path: Utility>Direction Config

See also:

320 - 327, 361 - 366

!

ATTENTION: Setting parameter 190 to 0 or 1 may cause unwanted motor
direction. Verify driven machinery cannot be damaged by reverse rotation
before changing the setting of this parameter to 0 or 1. Failure to observe
this precaution could result in damage to, or destruction of, equipment.