127 pi setpoint, 128 pi feedback sel, 129 pi integral time – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 60

4-28
LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Provides an internal fixed value for the process setpoint when PI Reference Sel (126)
is set to PI Setpoint.
Selects the source of the PI feedback signal.
Specifies the time required for the integral component to reach 100% of PI Error Meter
(137).
127
PI Setpoint
Range:
-/+100.00% of Maximum Process Value [0.01%]
Default:
50.00%
Access:
1
Path: Speed Command>Process PI
See also:
124-138
128
PI Feedback Sel
Range:
0 = PI Setpoint
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Master Ref
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Network
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
23 = Reserved
Default:
2 = Analog In 2
Access:
1
Path: Speed Command>Process PI
See also:
124-138
129
PI Integral Time
Range:
0.00 to 100.00 sec [0.01 sec]
Default:
2.00 sec
Access:
1
Path: Speed Command>Process PI
See also:
124-138