Parameter Descriptions

4-7

This parameter is not used with LiquiFlo 1.5 AC drives. The data output on the
analog output when configured for “Application” control.

This parameter is not used with LiquiFlo 1.5 AC drives. Selects how sequencing

will operate.

0 = The pre-charge is closed and voltage regulation is enabled when the inverter is

requested to start.

1 = The pre-charge is closed and voltage regulation is enabled when power is turned

on.

2 = The closing of the pre-charge and enabling of voltage regulation is controlled by

some other device writing directly into the rectifier control word.

3 = No rectifier is present in the system.

31

Appl Analog Output

Range:

4.000 to 20.000 [0.001 A]

Default:

4.000

Access:

1

Path: Monitor>Application

See also:

196

32

Rectifier Config

Range:

0 = Run at Start
1 = Run at Power Up
2 = Manual Control
3 = No Rectifier

Default:

3

Access:

1

Path: Monitor>Application

See also:

196