Parameter Descriptions
4-7
This parameter is not used with LiquiFlo 1.5 AC drives. The data output on the
analog output when configured for “Application” control.
This parameter is not used with LiquiFlo 1.5 AC drives. Selects how sequencing
will operate.
0 = The pre-charge is closed and voltage regulation is enabled when the inverter is
requested to start.
1 = The pre-charge is closed and voltage regulation is enabled when power is turned
on.
2 = The closing of the pre-charge and enabling of voltage regulation is controlled by
some other device writing directly into the rectifier control word.
3 = No rectifier is present in the system.
31
Appl Analog Output
Range:
4.000 to 20.000 [0.001 A]
Default:
4.000
Access:
1
Path: Monitor>Application
See also:
196
32
Rectifier Config
Range:
0 = Run at Start
1 = Run at Power Up
2 = Manual Control
3 = No Rectifier
Default:
3
Access:
1
Path: Monitor>Application
See also:
196