P.901 = fault (0) – Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual

Page 21

Advertising
background image

Drive Configuration

3-3

3.3.1 Setting NETW COMM LOSS SELECT (P.901)

(FlexPak 3000 Drives Only)

NETW

COMM

LOSS

SELECT

(P.901) is not used in WebPak 3000 drives. For

WebPak 3000 drives, a fault is generated when network communication is lost if

CONTROL

SOURCE

SELECT

(P.000) is set to

NETWORK

. This causes the drive to coast/DB

stop. The drive cannot be restarted until the fault is cleared.

For FlexPak 3000 drives,

NETW

COMM

LOSS

SELECT

(P.901) defines how the drive

responds to network communication loss when

CONTROL

SOURCE

SELECT

(P.000) is set

to network. Alarms do not cause the drive to stop. Therefore, some form of hardwired
stop must be available in case of communication loss since stopping the drive over the
network might not be possible.

You can set

NETW

COMM

LOSS

SELECT

(P.901) to

FAULT

(0),

USE

LAST

REF

(1),

USE

TRMBLK

REF

(2), or

USE

TRMBLK

CNTL

(3).

P.901 = FAULT (0)

When

NETW

COMM

LOSS

SELECT

(P.901) is set to

FAULT

and network communication is

lost, the following occurs:

The drive latches a fault condition and performs a coast/DB stop.

A

NETWORK

COMMUNICATION

LOSS

fault is generated.

When network communication is re-established, you must reset the fault before the
drive can be re-started. See the drive software manual for information on resetting
faults.

!

ATTENTION:

NETW

COMM

LOSS

SELECT

(P.901) allows you to configure

the drive to continue to run of a loss of network communication occurs.
You must provide some form of hardwired stop in case of communication
loss, since stopping the drive over the network might not be possible.
Failure to observe this precaution could result in bodily injury or damage
to, or destruction of, equipment.

!

ATTENTION: The drive is not equipped with a coast-stop pushbutton.
You must install a hardwired operator-accesible pushbutton that provides
a positive interrupt and shuts down the drive. Failure to observe this
precaution could result in bodily injury.

ATTENTION: If you are using the alternate register map (

NETW

REGISTER

MAP

SEL

(P.914) set to

ALTERNATE

) and you change the control source from

NETWORK

, the parameters

SPD

LOOP

PI

INIT

SEL

,

SPD

LOOP

PI

INIT

VAL

, and

SPD

LOOP

PI

RESET

are reset to their default values (0 for each). Ensure

these values are appropriate for your application before changing the
control source. Failure to observe this precaution could result in severe
bodily injury or loss of life.

Advertising