1 (con’t.), 10 to 15 – Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual

Page 54

Advertising
background image

6-

6

Aut

o

Max

Net

w

or

k Comm

unicat

ion
O

p

tion
B

oard

1 (con’t.)

13

Terminal strip auto/manual

14

Digital input 0

15

Motor thermostat

2

SPD

LOOP

REFERENCE

(P.295)

Final speed/voltage loop reference value

4095 at

TOP

SPEED

(P.011)

3

SPD

LOOP

FEEDBACK

(P.296)

Final speed/voltage loop feedback value after all scaling

4095 at

TOP

SPEED

(P.011)

4

SPD

LOOP

OUTPUT

(P.299)

Speed loop

PI

block output value

4095 at

MAXIMUM

CURRENT

(P.007)

5

ARMATURE

VOLTAGE

(P.289)

Armature voltage feedback value

4095 at

MOTOR

RATED

ARM

VOLTS

(P.009)

6

Average

CML

feedback

Current minor loop feedback average over 8

CML

scans

4095 at

MAXIMUM

CURRENT

(P.007)

7

Network Output Register 1

Value of the parameter selected by

NETW

OUT

REG

1

SELECT

(P.902)

If no valid parameter value selected,
0=motor speed in

RPM

8

Network Output Register 2

Value of the parameter selected by

NETW

OUT

REG

2

SELECT

(P.903)

If no valid parameter value selected,
0=armature voltage in volts

9

Network Output Register 3

Value of the parameter selected by

NETW

OUT

REG

3

SELECT

(P.904)

If no valid parameter value selected,
0=armature current in amps*10 or amps

10 to 15

Tunable, Configurable and Status Data

See table 6.4 on page 6-7.

16

ANALOG

AUTO

REFERENCE

(P.188)

Analog reference value in auto mode after all scaling

4095 at

TOP

SPEED

(P.011)

17

ANALOG

MAN

TRIM

REF

(P.194)

Analog manual trim reference input value

4095 at

TOP

SPEED

(P.011)

18

ANLG

IN

1 (P.492)

I/O Exp. kit analog input 1 after gain and zero applied

4095 at full scale

19

ANLG

IN

2 (P.493)

I/O Exp. kit analog input 2 after gain and zero applied

4095 at full scale

20

FREQ

IN

(P.491)

I/O Expansion kit frequency input value after all scaling

4095 at full scale

21

OCL

OUTPUT

(P.848)

Outer control loop output value

RPM

22

FIELD

FEEDBACK

(P.589)

Motor field current feedback value after scaling and gain 4095 at

MOTOR

HOT

FLD

AMPS

(P.510)

23

AC

LINE

VOLTAGE

(P.392)

Measured AC line

RMS

voltage

volts

RMS

*

The I/O Expansion kit digital inputs do not have fixed functions when

CONTROL

SOURCE

SELECT

(P.000) is set to

NETWORK

. Therefore, they do not select preset speeds, change the

MOP

setpoint, or enable or disable the

OCL

.

Table 6.3 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)

Register

Bit

Parameter Name (Number)

Description

Settings

Runtime signal data are updated by the regulator every 5 msec, unless