FlexPak 3000 Drives: Alternate Register Map

6-1

C

HAPTER

6

FlexPak 3000 Drives:

Alternate Register Map

This section lists the alternate register map, which enables you to access most of the
FlexPak 3000 original register map functions plus some additional functions. The
alternate register map is organized so that commonly used functions are available in
Drop_1. It also offers a different set of options in Drop_1 than the original register
map.

The additional functions that are available through the alternate register map are:

Winding functions:

SPEED

FEEDBACK

GAIN

(Drop_1, register 38) and

UNDERWIND

ENABLE

(Drop_1, register 32, bit 5) enable you to set up under- or overwinding and

set the gain of the speed loop feedback path for winding applications.

Access to the speed loop

PI

reset and initial value. These parameters are

SPD

LOOP

PI

INIT

SEL

(Drop_2, register 32),

SPD

LOOP

PI

INIT

VAL

(Drop_1, register 39), and

SPD

LOOP

PI

RESET

(Drop_1, register 32, bit 6).

Process Error Parameter Number (Drop_1, register 27)

NETW

REGISTER

MAP

SEL

(P.914) (Drop_1, register 29)

RAMP

STOP

DECEL

TIME

(P.018) (Drop_2, register 33)

INV

FLT

AVOID

SEL

(P.312) (Drop_2, register 43)

TACH

LOSS

SCR

ANGLE

(P.608), (Drop_3, register 50)

NEG

CUR

LIM

INV

EN

(P.226) (Drop_3, register 53, bit 0)

OCL

PROP

TRIM

SELECT

(P.813) (Drop_3, register 53, bit 1)

OCL

TYPE

3

POSN

REG

EN

(P.814) (Drop_3, register 53, bit 2)

PHASE

LOSS

DETECT

EN

(P.609) (Drop_3, register 53, bit 3)

STOP

DECEL

SELECT

(P.122) (Drop_3, register 53, bit 4)

CML

REF

LIMIT

SELECT

(P.311) (Drop_3, register 53, bit 6

DIG

IN

0

SELECT

(P.428) (Drop_4, register 47)

Brief descriptions of parameters are in the register map tables. For detailed parameter
descriptions, refer to the

FlexPak 3000 DC Drive Software Reference Manual

.

!

ATTENTION: If you are using the alternate register map (

NETW

REGISTER

MAP

SEL

(P.914) set to

ALTERNATE

) and you change the control source

from

NETWORK

, the parameters

SPD

LOOP

PI

INIT

SEL

,

SPD

LOOP

PI

INIT

VAL

,

and

SPD

LOOP

PI

RESET

are reset to their default values (0 for each). Make

sure these values are appropriate for your application before changing
the control source. Failure to observe this precaution could result in
severe bodily injury or loss of life.