Table 5.3 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)

Register

Bit

Parameter Name (Number)

Description

Settings

10

Fault latch bits word 1

Bit-packed word indicating latched faults

0

AC

LINE

SYNCHRONIZATION

FAULT

(F00010)

1

FIELD

CURRENT

LOSS

(F00004)

2

SUSTAINED

OVERLOAD

(F00005)

3

SELF

TUNING

FAULT

(F00060 to F000099)

4

MOTOR

THERMOSTAT

TRIP

(F00008)

5

CONTROLLER

THERMOSTAT

TRIP

(F00009)

6

BLOWER

MOTOR

STARTER

OPEN

(F00006)

7

Reserved

8

IET

(

OVERCURRENT

) (F00001)

9

OVERSPEED

(F00003) /

ARMATURE

OVERVOLTAGE

(F00012)

10

SCR

N

or

MULTIPLE

SCRS

NOT

OPERATING

(F00030–F00042)

11

OPEN

ARMATURE

(F00007)

12

TACHOMETER

LOSS

(F00002)

13

OIM

COMMUNICATIONS

TIMEOUT

(F00011)

14

NETWORK

COMMUNICATION

TIMEOUT

(F00013)

15

REVERSED

TACH

LEADS

(F00014)

11

Reserved

12

First fault

Fault code of the first fault since the last fault reset

13

Alarm latch bits word

Bit-packed word containing latched alarm bits

0

MOTOR

BRUSH

WEAR

LOW

(A00001)

1

AC

LINE

VOLTAGE

LOW

(A00002)

2

AC

LINE

VOLTAGE

HIGH

(A00003)

3 to 15

Reserved

14

Last alarm

Alarm code of the most recent alarm

15

CONTROL

SOURCE

SELECT

(P.000)

Selected source for drive control signals

0=

TERMBLK

; 1=

KEYPAD

; 2=

SERIAL

; 3=

NETWORK

16

ACCELERATION

TIME

(P.001)

Min. time to accelerate from zero to

TOP

SPEED

(P.011)

seconds * 10

17

DECELERATION

TIME

(P.002)

Min. time to decelerate from

TOP

SPEED

(P.011) to zero

seconds * 10

Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.