AutoMax Network Communication Option Board

P.901 = USE LAST REF (1)

When

NETW

COMM

LOSS

SELECT

(P.901) is set to

USE

LAST

REF

and network

communication is lost, the following occurs:

The drive continues to run, using the last reference received from the network
master.

A

NETWORK

COMMUNICATION

TIMEOUT

alarm (A00004) is generated.

An entry is made into the drive’s alarm log for each active-to-inactive transition of
network communication status.

If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.

You can stop the drive using the hardwired stop input or the

OIM

STOP

/

RESET

key.

However, you cannot restart the drive until network communication is re-established or

CONTROL

SOURCE

SELECT

(P.000) is changed.

P.901 = USE TRMBLK REF (2)

When

NETW

COMM

LOSS

SELECT

(P.901) is set to

USE

TERMBLK

REF

(2) and network

communication is lost, the following occurs:

The drive continues to run, using the auto reference value selected by

AUTO

REFERENCE

SELECT

(P.103)

(or Regulator board terminals 19 and 20?)

A

NETWORK

COMMUNICATION

TIMEOUT

alarm (A000014) is generated.

If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.

You can stop the drive using the hardwired stop input, the

OIM

STOP

/

RESET

key, or the

hardwired stop input (coast/DB stop, Regulator board terminal 8). However, you
cannot restart the drive until network communication is re-established or

CONTROL

SOURCE

SELECT

(P.000) is changed.

P.901 = USE TRMBLK CNTL (3)

When

NETW

COMM

LOSS

SELECT

(P.901) is set to

USE

TRMBLK

CNTL

(3), and network

communication is lost, the following occurs:

The drive continues to run using the Regulator board terminal strip as the source for
all control (run, jog, stop, fault reset, direction, and OCL enable) and speed (auto)
reference signals.

A

NETWORK

COMMUNICATION

TIMEOUT

alarm (A000014) is generated.

The Speed Loop PI Reset and Underwind/Overwind bits cannot be changed while
operating in this mode. They will remain at the last values received from the
network.

If network communication is re-established and the drive is still running, the drive will
again frollow the reference and sequencing control inputs supplied by the network
master.