Table 5.15 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)

Register

Bit

Parameter Name (Number)

Description

Settings

0

I/O Expansion kit digital inputs

Bit-packed word that indicates the state of these inputs

*

*

The I/O Expansion kit digital inputs do not have fixed functions when

CONTROL

SOURCE

SELECT

(P.000) is set to

NETWORK

. Therefore, they do not select preset speeds,

change the

MOP

setpoint, or enable or disable the

OCL

.

0

I/O Expansion kit digital input 1 (Preset speed select 1)*

1

I/O Expansion kit digital input 2 (Preset speed select 2)*

2

I/O Expansion kit digital input 3 (mop decrement)*

3

I/O Expansion kit digital input 4 (mop increment)*

4

I/O Expansion kit digital input 5 (ocl enable)*

1

ANLG

IN

1 (P.492)

I/O Exp. kit analog input 1 after gain and zero applied

4095 at full scale

2

ANLG

IN

2 (P.493)

I/O Exp. kit analog input 2 after gain and zero applied

4095=full scale

3

FREQ

IN

(P.491)

I/O Expansion kit frequency input value after all scaling

4095=full scale

4 to 20

Reserved

Runtime signal data are updated by the regulator every 5 msec, unless

FEEDBACK

SELECT

(P.200) is set to

ARMATURE

VOLT

, in which case the update time is 10 msec.

Table 5.16 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)

Register

Bit

Parameter Name (Number)

Description

Settings

21

Level Detector Outputs

Bit-packed word indicating state of level detector outputs

0

Level detector 1 output

1

Level detector 2 output

Tunable, configurable and status data are updated by the regulator approximately every 600 msec.