1 i/o update enable logic summary, Figure 4.1 - i/o update enable logic strings, 4 setting up data types that can be transferred – Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual

Page 25: Set the tune/config input enable bit to 1

Advertising
background image

Programming

4-3

4.3.1 I/O Update Enable Logic Summary

The logic strings shown in figure 4.1 summarize the output and input enable logic
described in this chapter.

4.4

Setting Up Data Types That Can Be Transferred

You must enable the transfer of tunable and configurable inputs from the Network
Option board to the Regulator board. Until you enable transfer, only control/reference
data are read by the Regulator board.

To enable transfer of tunable and configurable data, set the network-master-controlled
Tune/Config Input Enable bit (Drop_1, register 32, bit 14) to 1.

For example, the master application program would typically:

1.

Initialize the tunable and configurable input data in the dual-port memory of the
master’s Network module

2.

Delay for an appropriate amount of time to ensure data have been transferred to
the drive

3.

Set the Tune/Config Input Enable bit to 1.

If you only want to transfer control/reference data, leave the Tune/Config Input Enable
bit at 0 (off). This forces you to configure the drive through another source, such as the

OIM

, CS3000 software, or WebPakCS software, but allows you to control the drive

(including

RUN

,

JOG

,

STOP

,

RESET

, and the reference) from the network master.

Figure 4.1 – I/O Update Enable Logic Strings

Outputs

CONTROL SOURCE

NETW COMM STATUS
(P.908) = ACTIVE

Control/Reference

Inputs Read

Tune/Config
Input Enable

Tunable
Inputs Read

Running

Jogging

Configurable
Inputs Read

Updated

SELECT = NETWORK