Motor field current feedback value after scaling and gain 4095 at

MOTOR

HOT

FLD

AMPS

(P.510)

25

AC

LINE

VOLTAGE

(P.392)

Measured AC line

RMS

voltage

Volts

RMS

Table 7.4 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)

Register

Bit

Parameter Name (Number)

Description

Settings

11

Fault latch bits word 1

Bit-packed word indicating latched faults

0

AC

LINE

SYNCHRONIZATION

FAULT

(F00010)

1

FIELD

CURRENT

LOSS

(F00004)

2

SUSTAINED

OVERLOAD

(F00005)

3

SELF

TUNING

FAULT

(F00060 to F000099)

4

MOTOR

THERMOSTAT

TRIP

(F00008)

5

CONTROLLER

THERMOSTAT

TRIP

(F00009)

6

BLOWER

MOTOR

STARTER

OPEN

(F00006)

7

Reserved

8

IET

(

OVERCURRENT

) (F00001)

9

OVERSPEED

(F00003) /

ARMATURE

OVERVOLTAGE

(F00012)

10

SCR

N

OR

MULTIPLE

SCRS

NOT

OPERATING

(F00030 to

F00042)

11

OPEN

ARMATURE

(F00007)

12

TACHOMETER

LOSS

(F00002)

13

OIM

COMMUNICATIONS

TIMEOUT

(F00011)

14

NETWORK

COMMUNICATION

TIMEOUT

(F00013)

15

REVERSED

TACH

LEADS

(F00014)

12

Reserved

13

First fault

Fault code of the first fault since the last fault reset

Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.

Table 7.3 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)

Register

Bit

Parameter Name (Number)

Description

Settings

Runtime signal data are updated by the regulator every 10 msec.