Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual

Page 40

Advertising
background image

5-

10

Aut

o

Max

Net

w

or

k Comm

unicat

ion
O

p

tion
B

oard

43

Reserved

44

ANLG

MAN

REF

GAIN

ADJ

(P.104)

Scales the analog manual reference gain

gain * 1000

45

ANLG

MAN

REF

ZERO

ADJ

(P.105)

Offset removed from the analog manual reference signal

46

TRIM

REFERENCE

SELECT

(P.108)

Trim reference selection

0=

REGISTER

; 1=

ANALOG

MANUAL

;

2=

ANALOG

IN

1; 3=

NETW

IN

REG

1;

4=

NETW

IN

REG

2; 5=

NETW

IN

REG

3;

6=

ANALOG

IN

2

47

TRIM

MODE

SELECT

(P.110)

Type of trim mode selected

0=

NO

TRIM

; 1=

INCREMENTAL

; 2=

PROPORTIONAL

48

AUTO

MODE

MIN

BYPASS

(P.111)

Disables minimum speed limit while in auto mode

0=

OFF

; 1=

ON

(min speed bypassed)

49

AUTO

MODE

RAMP

BYPASS

(P.112)

Bypasses speed loop S-curve block while drive is in auto 0=

OFF

; 1=

ON

(rate limit bypassed)

50

STOP

SPEED

THRESHOLD

(P.113)

Speed threshold at which the main contactor will open
during a controlled stop

RPM

51

OCL

PI

PROP

GAIN

(P.808)

OCL

PI

block proportional gain

gain * 100

52

OCL

PI

LEAD

FREQ

(P.809)

Outer control loop

PI

block lead break frequency

radians/second * 100

53

OCL

PI

POSITIVE

LIMIT

(P.810)

OCL

PI

block positive limit

%

54

OCL

PI

NEGATIVE

LIMIT

(P.811)

Outer control loop

PI

block negative limit

%

55

OCL

TRIM

RANGE

(P.812)

Trim range for the

OCL

% * 10

Table 5.10 – FlexPak 3000 Original Register Map, Drop_2: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data)

Register

Bit

Parameter Name (Number)

Description

Settings

56

INERTIA

COMP

SELECT

(P.221)

Source of inertia compensation

0=

NONE

; 1=

INTERNAL

; 2=

ANALOG

IN

1;

3=

ANALOG

IN

2; 4=

NETW

IN

REG

1 (P.905);

5=

NETW

IN

REG

2 (P.906); 6=

NETW

IN

REG

3 (P.907)

57

POS

CURRENT

LIM

SEL

(P.223)

Selects positive current limit source

0=

REGISTER

; 1=

ANALOG

IN

1; 2 =

ANALOG

IN

2; 3=

NETW

IN

REG

; 4=

NETW

IN

REG

2;

5=

NETW

IN

REG

3

58

NEG

CURRENT

LIM

SEL

(P.224)

Selects negative current limit source

59

OCL

REFERENCE

SELECT

(P.800)

Selects

OCL

reference source

0=

REGISTER

; 1=

ANALOG

IN

1; 2 =

ANALOG

IN

; 3=

FREQUENCY

IN

; 4=

NETW

IN

REG

1;

5=

NETW

IN

REG

2; 6=

NETW

IN

REG

3

Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit =1 and the drive is not running or jogging.

Table 5.9 – FlexPak 3000 Original Register Map, Drop_2: Master Write Registers, FULL Connection. Tunable Data (Drive Input Data) (Continued)

Register

Bit

Parameter Name (Number)

Description

Settings

Tunable data are updated by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.