Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual

Page 59

Advertising
background image

F

lex
Pak

3000 Drives

: Alt
e

rnat
e Regist

er
M

a

p

6-

11

Table 6.8 – FlexPak 3000 Alternate Register Map, Drop_2: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)

Register

Parameter Name (Number)

Description

Settings

0

SPD

SOURCE

SELECT

OUT

(P.193)

Selected speed/voltage loop reference value

4095 at

TOP

SPEED

(P.011)

Runtime signal data are updated by the regulator every 5 msec, unless

FEEDBACK

SELECT

(P.200) is set to

ARMATURE

VOLT

, in which case the update time is 10 msec.

Table 6.9 – FlexPak 3000 Alternate Register Map, Drop_2: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)

Register

Bit

Parameter Name (Number)

Description

Settings

1

ACCELERATION

TIME

(P.001)

Min. time to accelerate from zero to

TOP

SPEED

(P.011)

seconds * 10

2

DECELERATION

TIME

(P.002)

Min. time to decelerate from

TOP

SPEED

(P.011) to zero

seconds * 10

3

MINIMUM

SPEED

(P.003)

Lowest operating speed

RPM

4

MAXIMUM

SPEED

(P.004)

Highest operating speed

RPM

5

POSITIVE

CURRENT

LIM

(P.005)

Highest amount of current for the forward bridge

% of

MOTOR

RATED

ARM

AMPS

(P.008)

6

NEGATIVE

CURRENT

LIM

(P.006)

Highest amount of current for reverse bridge

% of

MOTOR

RATED

ARM

AMPS

(P.008)

7

TRIM

RANGE

(P.109)

Amount the trim reference will affect the drive reference

%

8

SPD

LOOP

PI

PROP

GAIN

(P.211)

Speed loop

PI

proportional gain

gain * 100

9

SPD

LOOP

PI

LEAD

FREQ

(P.212)

Speed loop

PI

block lead break frequency

radians/second * 100

10

Reserved

11

OCL

RAMP

OUTPUT

(P.846)

OCL

reference S-curve block output

4095

12

Reserved

13

TOP

SPEED

(P.011)

Highest running speed of motor

RPM

14

JOG

SPEED

1 (P.012)

Operating speed while jogging

RPM

15

JOG

ACCEL

/

DECEL

TIME

(P.013)

Minimum time in which jog reference can go from zero to

TOP

SPEED

(P.011) and from

TOP

SPEED

to zero

seconds * 10

16

S

-

CURVE

ROUNDING

(P.014)

Smoothing of the speed/voltage loop reference

%

17

REVERSE

DISABLE

(P.015)

Prevents speed/voltage loop ref. from going negative

0=

OFF

(bipolar ref); 1=

ON

(positive ref)

18

ANLG

AUTO

SIGNAL

TYPE

(P.100)

Type of signal applied to analog auto reference input

0=0–10V; 1=±10V; 2=4-20mA; 3=10-50mA

19

ANLG

AUTO

GAIN

ADJ

(P.101)

Scales analog auto reference signal

gain * 1000

20

ANLG

AUTO

ZERO

ADJ

(P.102)

Offset removed from analog auto reference zero

21

AUTO

REFERENCE

SELECT

(P.103)

Selects the type of auto reference

0=

ANALOG

; 1=

FREQUENCY

IN

22

ANLG

MAN

REF

GAIN

ADJ

(P.104)

Scales the analog manual reference gain

gain * 1000

Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.