7-

16

Aut

o

Max

Net

w

or

k Comm

unicat

ion
O

p

tion
B

oard

23

SPEED

RAMP

OUTPUT

(P.199)

Value of the speed reference signal immediately after the
speed loop

S

-

CURVE

block

24

TAPER

PERCENT

(P.859)

Percent reduction to be applied to the tension reference
from the taper function

25

TEN

LOOP

ERROR

(P.834)

Tension/current loop error signal after scaling

26

TEN

PI

KP

OUT

(P.879)

Value of the tension loop pi proportional gain

27

TEN

RAMP

OUTPUT

(P.842)

Output of the tension major loop ramp block after
tension-to-current conversion

28

TEN

TO

CURRENT

OUT

(P.876)

Output of the tension loop’s tension-to-current scaling
block

29

TRIM

OUTPUT

(P.197)

Actual signal used to trim the selected speed loop
reference signal

30

UNWIND

DIAMETER

IN

(P.828)

Analog input signal (TB 16, 17) when

DIAMTER

/

TAPER

SELECT

(P.870) =

DIAMETER

31

Indirect Register Status

Bit-packed word containing information on

0 to 6

Offending register number.

0 = No error

7 to 12

Reserved

13

Error - Not found

14

Error - Output parameter

15

Network sync

Table 7.12 – WebPak 3000 Register Map, Drop_3: Master Write Registers, FULL Connection. Tunable/Configurable Data (Drive Input Data)

Register

Bit

Parameter Name (Number)

Description

Settings

32

AutoMax Indirect Register 1

Value to be written to the parameter selected in the
corresponding Drop 2 register

33

AutoMax Indirect Register 2

Value to be written to the parameter selected in the
corresponding Drop 2 register

34

AutoMax Indirect Register 3

Value to be written to the parameter selected in the
corresponding Drop 2 register

Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.

Table 7.11 – WebPak 3000 Register Map, Drop_3: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data) (Continued)

Register

Bit

Parameter Name (Number)

Description

Settings

Runtime signal data are updated by the regulator every 10 msec.