WebPak 3000 Drives: Register Map

7-3

7.2

Diagnosing Processing Errors

In the alternate map, Drop_1, register 27, the number of the parameter that caused a
processing error (indicated by alternate map, register 0, bit 10) is now recorded. If
there are no processing errors, the value will be set to -1.

Because some parameters are processed in groups, it is not possible to always report
the specific parameter that is out of range. Instead, the first parameter number of the
group that contains the error is reported (see table 7.1).

For example, if

MOP

ACCEL

TIME

(P.115) was set out of range by the Network Option board, Drop_1, register

27 would contain the value 14 (

S

-

CURVE

ROUNDING

).

Parameters not listed in table

7.1 are handled on an individual basis by the parameter processing routines so the
parameter causing the processing error is reported by number directly. Also listed in
the table are possible non-user parameter numbers (

≥ 25000) that can cause

parameter processing errors.

Be aware that certain parameters are used as limits for other parameters (for example,

TOP

SPEED

(P.011) determines the maximum limit for

MAXIMUM

SPEED

(P.004).

The

WebPak 3000 Software Reference (D2-3444) describes the relationships between all
user parameters. It is also possible (but very unlikely) to get a processing error
reported for a non-user parameter number not listed below. If this occurs, the
Regulator board is suspect. Cycle power, and if another non-user parameter number
processing error occurs, replace the Regulator board.

Table 7.1 – Error Processing Parameters Reported by Group

Number

Reported

Parameter

Number

Parameter Name

Number

Reported

Parameter

Number

Parameter Name

004

004
003
012
113

MAXIMUM

SPEED

MINIMUM

SPEED

JOG

SPEED

1

STOP

SPEED

THRESHOLD

519

519
520

FLD

WEAKEN

PROP

GAIN

FLD

WEAKEN

LEAD

FREQ

005

005
006

POSITIVE

CURRENT

LIM

NEGATIVE

CURRENT

LIM

803

803
802

OCL

REF

ROUNDING

OCL

REF

RAMP

TIME

213

213
214

SPD

LEADLAG

RATIO

SPD

LEADLAG

LOW

FREQ

807

807
806

OCL

LEADLAG

RATIO

OCL

LEADLAG

LOW

REQ

014

014
001
002
018
013

S

-

CURVE

ROUNDING

ACCELERATION

TIME

DECELERATION

TIME

RAMP

STOP

DECEL

TIME

JOG

ACCEL

/

DECEL

TIME

900

900
910

NETW

DROP

NUMBER

NETW

CONNECT

TYPE

424

424
423

FREQ

IN

FULL

SCALE

FREQ

IN

ZERO

902

902
903
904

NETW

OUT

REG

1

SELECT

NETW

OUT

REG

2

SELECT

NETW

OUT

REG

3

SELECT

427

427
426

FREQ

OUT

FULL

SCALE

FREQ

OUT

ZERO

25200

25200

Trending Aquisition Rate
(set by WebPakCS)

510

510
516

MOTOR

HOT

FLD

AMPS

FLD

FEEDBACK

GAIN

ADJ

26015

SPD

LOOP

PI

INIT

SEL

(alternate, Drop_2,
reg 32)

514

514
515

FIELD

PI

PROP

GAIN

FIELD

PI

LEAD

FREQ