Trial Operation

6 -16

6.5 Speed Control Mode Adjustment Procedure

First check that the Motor is operating normally, and then adjust the speed control mode according to the adjust-

ment procedure shown below. Also, if replacing the Motor or Inverter, be sure to perform the adjustments

shown below.

Adjustment Item and Procedure

Details

Adjust C1-12 (S

ADJ

) to

smaller than current value.

NO

NO

YES

YES

Turn ON the power supply.

Make initial settings.

Turn ON emergency stop (EMG)

and operation standby (RDY).

Enter the rated speed reference.

Trun ON forward rotation (PWD).

Digital

Analog

Is speed

reference analog

or digital?

After acceleration is completed,

check the motor speed using U1-01.

Does

motor speed

agree with the ref-

erence?

Higher than reference?

Adjust C1-12 (S

ADJ

) to

smaller than current value.

(1)

Initial Settings

S

Check the settings according to the factory settings table.

RUN Operation (0 V Common)

7

EMG

RDY

FWD

0VCOM

EXTCOM

24VCOM

6

8

24

19

22

3

4

SCOM

0 V

10 V / 100%

Stop

RUN

Check input signal.

S

Input signal status (U1-09)

Motor speed adjustment value (C1-12)

RDY, EMG, and FWD are lit.

(P.U.)

1.1

1.0

0.9

0

0.9

1.0

1.1 (C1−12)

Example: When reference speed = 6,000 min

−1

and actual speed =

6,060 min

−1

., C1-12 = 6,000/6,060 = 0.99

Speed

C1-12 = Reference speed/Actual motor speed

(Continued on next page.)

6