Wide Constant Power Control Using Winding Selection

7.5.2 Automatic Winding Selection methods

7 -8

7.5.2 Automatic Winding Selection methods

This section explains the automatic winding selection methods. There are two methods.

J

Using the Inverter Speed Detection Signal

The flowchart and timing chart for performing automatic winding selection judging from the actual motor

speed alone using the Inverter speed detection signal (SDET) are shown below.

Start

Motor speed ≥

S

CHW

+ nS

(SDET) OFF

Low-speed winding?

Select high-speed coil.

(CHW Turns OFF.)

Winding selection

completed

(CHWE)?

End

Motor speed ≤

S

CHW

− nS

(SDET) ON

High-speed winding?

Select low-speed winding

(CHW Turns ON.)

Winding selection

completed

(CHWE)?

YES

YES

YES

NO

NO

NO

YES

YES

YES

NO

NO

NO

* 1. Operations within the dotted lines are Inverter internal signal processes.
* 2. S

CHW

: Winding selection speed (Motor) (Set using control constant C1-21 (SD

LVL

).)

∆S: Switching speed hysterisis width (Set using control constant C1-22 (SD

HYS

).)

Set S

CHW

and

∆S as shown below.

Within the diagram,
S

CHW

∆S

≧ S

BH

S

CHW

+

∆S

≦ S

BH

S

CHW

S100 (C1-26)

× 100(%)

C1−21=

ΔS

S100 (C1-26)

× 100(%)

C1−22=

(Where

∆S = 100 to 200 min

−1

)

Refer to Chapter 5 Operating the Digital Operator for details on the setting methods.

Fig 7.6

Flowchart

7

−nS

S

CHW

(C1-21)

+nS

ON

OFF

[SDET]