Yaskawa Varispeed 626M5 User Manual

Page 190

Advertising
background image

12 - 6

Table 12.2

Inverter Faults (continued)

Fault No.

Name

Contents

Corrective Actions

Error Code

Main circuit
undervoltage

Main circuit DC bus voltage became
lower than undervoltage detection
level during run.

Check the input supply voltage.

FFFf

Control cir-
cuit under-
voltage

Control circuit power supply became
lower than undervoltage detection
level.

Check the control supply voltage.

FFFf

Winding
selection
fault

Winding selection was not completed
within set time.

S

Check the control constant

C1-25.

S

Check magnetic contactor wir-

ing for winding selection.

FFfF

Emergency
stop fault

Inverter did not stop within 10 se-
conds after emergency stop com-
mand.

S

Check control constant C1-25.

S

Check the setting of control

constant C1-24 and whether ex-

ternal torque limit signals TLL

and TLH are input.

FFfF

Encoder sig-
nal cable dis-
connection

Motor encoder signal was discon-
nected or connected improperly.

Check the wiring of encoder sig-
nal lines.

FFff

Motor over-
speed

Motor speed exceeded 120% of set
rated speed.

S

Confirm that encoder signal

lines are separated from main

circuit or other power lines.

S

Check the control constants.

FFff

Excessive
speed devi-
ation

Speed falls to less than 50% of refer-
ence value.

S

Check if the load is heavy or a

tool is jammed.

S

Check whether external torque

limit signals TLL and TLH are

input.

S

Check the control constants.

S

Check the wiring of encoder sig-

nal lines.

FFff

Load fault

Inverter output (U/T1, V/T2, W/T3)
was disconnected.

Check Inverter output wiring.

FFff

Motor Lock
Detection
(For IP mo-
tors only)

The motor is locked. (The motor
speed remains at 35 min

−1

or lower

for 10 seconds during the torque
reference saturation.)

S

Check if the load is heavy or a

tool is jammed.

S

Check the wiring between In-

verter and motor.

S

Check the wiring of encoder sig-

nal lines.

S

Make sure that the motor shaft

rotates.

S

Check if a motor fault or a con-

tact between rotor and stator oc-

curs, or if a bearing is damaged.

FFff

Motor over-
heat 1

Motor temperature exceeded upper
limit (minor fault).

S

Check the wiring.

S

Confirm that motor cooling air is

normal with power ON.

C fi

th t th f

i

t

FfFF

Motor over-
heat 2

Motor temperature over upper limit
continued for over one minute.

S

Confirm that the fan is not

clogged with dust or oil.

S

Check the wiring of motor

thermistor signal lines.

FfFF

12

Troubleshooting