7.4 Winding Selection Operation

7 -5

7.4 Winding Selection Operation

The timing chart for switching from low-speed to high-speed windings is shown in the following diagram.

Approx. 170 ms

Winding selection signal (CHW)

Gate block

Gate block

Magnetic contactor for winding

selection

Winding

Auxiliary

contact

Winding selection completion signal

(CHWE)

Control constant

Motor current

Low-speed constant

High-speed constant

Approx. 30 ms

Preparing to switch

Switching Reset after switching

Reference

Completed

ON

OFF

OFF

OFF

ON

ON

ON

100 ms

2CN

2CN

10-11

12-13

Note: The auxiliary contact (2CN terminals 12-13) of the magnetic contactor for winding selec-

tion can be checked using control signal U1-09. When the auxiliary contact is ON, CHWA

of U1-09 is lit.

Fig 7.3

Winding Selection Timing Chart