15.5.2 Heat Exchanger Specifications

15 -24

15.5.2 Heat Exchanger Specifications

To improve the cooling abilities of the control panel, install one of the Heat Exchangers (manufactured

by Yaskawa) shown in Table 15.8.

Table 15.7 Heat Exchanger Specifications

Heat Exchanger

Cooling Ability

Dimensions

(mm (inches))

Mounting Surface

(m

2

)

REX1550

110 W/10°C (50°F)

295 x 890 x 50 (11.6 x 35 x 1.97)

(W x H x D)

0.31

HEATEX02

250 W/10°C (50°F)

440 x 924 x 50 (17.3 x 36.4 x 1.97)

(W x H x D)

0.45

The calorific content of the Cooling Ability column is the calorific tolerance when the internal air tempera-

ture rise within the unit is suppressed to 10 K (10 °C (50°F)) max.
Mount the heat exchanger internally as shown in Fig. 15.28 so that the internal air is drawn in from the

top and expelled through the bottom, and so that the external air is drawn in from the bottom and expelled

from the top.

External air

flow

Top

Case

Internal air

flow

Heat exchanger

Bottom

Fig 15.28 Example of Heat Exchanger Mounting