Yaskawa Varispeed 626M5 User Manual

Page 89

Advertising
background image

Control Signals

4.4.4 Details on Sequence Output Signals

4-14

J

SDET (Speed Detection Signal)

Connector number: 6CN

Pin numbers:

35

42

D

The SDET signal will turn ON when the motor speed reaches the preset value or less.

D

The speed detection level is set between 0% and 100% in the C1-21 (SD

LVL

) control constant.

Speed

Time

Detection

level

(C1−21)

ON

OFF

ON

D

Set the hysteresis width of the SDET signal in the C1-22 (SD

HYS

) control constant.

D

The SDET operates regardless of the operation signal.

J

TDET (Torque Detection Signal)

Connector number: 6CN

Pin numbers:

36

42

D

The TDET signal will turn ON when the torque reference reaches the preset value or less.

D

Once TDET turns OFF, the status is held for 50 ms.

D

The torque detection level is set between 5% and 120% of the 30-minute rating for the C1-23 (TD

LVL

)

time constant. There is an hysteresis of ±10% of the set value for the operation point.

D

Bit 2 of selection signals C1-40 (SEL5) can be turned ON to prevent TDET from turning OFF even

if the torque references exceeds the set value during acceleration and deceleration.

D

The TDET signal can be used to check the operation of the torque limit or load.

J

TLE (Torque Control Signal)

Connector number: 6CN

Pin numbers:

37

42

D

The TLE signal turns ON when the TLL or TLH torque control signal turns ON.

D

The TLE signal can be used to check the TLL or TLH signal.

4