14.3.8 Surge Absorbers

14 -68

14.3.8 Surge Absorbers

Always use a surge absorber (recommneded manufacturer: Marcon Electronics) with inductive loads,

such as magnetic contactors, magnetic relays, magnetic valves, solenoids, and magnetic brakes, that are

connected near the Inverter.
The surge absorber absorbs energy accumulated in the coils of the magnetic contactor, and so requires a

capacity equal to that of the coils. Never connect the surge absorber to the Inverter output terminals (U,

V, and W).

Failure to connect a surge absorber means that there is a risk of signal failure because the surge voltage gener-

ated by the coils when the magnetic contactor is turned ON and OFF can affect the Inverter control signal

wires.

J

Specifications and Model Numbers

The surge absorber specifications and model numbers are shown in the following table.

Device

Surge Absorbers

Model

Specifications

Code Number

200 to 230 V

Large-capacity coil other than a

relay

DCR2-50A22E

220 VAC

0.5 µF + 200 Ω

C002417

Control relay

LY-2, LY-3,

HH-22, HH-23,

MM2, MM4

DCR2-10A25C

250 VAC

0.1 µF + 100 Ω

C002482

380 to 460 V device

DCR2-50D100B 1000 VDC

0.5 µF + 220 Ω

C002630

J

Dimensions

The surge absorber dimensions are shown in the following diagram.

9

(0.35)

φ4.8

24

(0.94)

30

(1.18)

36

(1.42)

φ18

30

(1.18)

16

(0.63)

16

(0.63)

22.5

(0.89)

φ0.8

26

68 (2.68)

33

(1.3)

34

(1.34)

76 (2.99)

692−241

7

(0.28)

Two 4-dia

mounting holes

Details of

mounting holes

2-3 tap

Lead 910

Weight: 22 g

Weight: 5 g

Weight: 150 g

DCR2-50A22E

DCR2-10A25C

DCR2-50D100B

Unit: mm (inches)

Lead 250

(1.02)

14