Wiring

3.3.1 Wires and Suitable Crimp Connectors

3 -10

Table 3.4

400 V Class Inverter Power Cable Specifications

Wire Sizes

Model CIMR-

M5

Terminal Symbols

Terminal

Screw

Tighten-

ing

Torque

(N S m)

UL-approved

75°C (167°F)

Temperature-rated

Copper Wire

[AWG (mm

2

)]

600 V Vinyl-

sheath Insulated

Wire (IV, VV)

60°C (140°F)

(mm

2

)

600 V Cross-

linked Polyethy-

lene Wire (IC)

90°C (194°F)

(mm

2

)

600 V Rubber-in-

sulated Cabtyre

Cable (CT)

60°C (140°F)

(mm

2

)

P/¨, N/©

M6

2.94

(*1)

45P5

U/T1, V/T2, W/T3

M5

2.35

12 (3.3)

2

2

2

M5 × 2

2.35

10 (5.3)

3.5

2

3.5

P/¨, N/©

M6

2.94

(*1)

47P5

U/T1, V/T2, W/T3

M5

2.35

12 (3.3)

3.5

2

3.5

M5 × 2

2.35

10 (5.3)

3.5

2

3.5

P/¨, N/©

M6 × 2

2.94

(*1)

4011

U/T1, V/T2, W/T3

M6

3.4 to 4.9

10 (5.3)

5.5

2

5.5

4011

M5 × 2,

2.1 to 2.5

10 (5 3)

3 5

2

3 5

M5 × 2,

M6

3.4 to 4.9

10 (5.3)

3.5

2

3.5

P/¨, N/©

M6 × 2

2.94

(*1)

4015

U/T1, V/T2, W/T3

M6

3.4 to 4.9

8 (8.4)

8

3.5

8

4015

M5 × 2,

2.1 to 2.5

8 (8 4)

5 5

3 5

5 5

M5 × 2,

M6

3.4 to 4.9

8 (8.4)

5.5

3.5

5.5

P/¨, N/©

M6 × 2

2.94

(*1)

4018

U/T1, V/T2, W/T3

M6

3.4 to 4.9

8 (8.4)

14

5.5

14

4018

M5 × 2,

2.1 to 2.5

8 (8 4)

8

5 5

5 5

M5 × 2,

M6

3.4 to 4.9

8 (8.4)

8

5.5

5.5

P/¨, N/©

M6 × 2

2.94

(*1)

4022

U/T1, V/T2, W/T3

M6

3.4 to 4.9

6 (13.3)

14

8

14

4022

M5 × 2,

2.1 to 2.5

8 (8 4)

8

5 5

5 5

M5 × 2,

M6

3.4 to 4.9

8 (8.4)

8

5.5

5.5

P/¨, N/©

M6 × 2

2.94

(*1)

4030

U/T1, V/T2, W/T3

M8

7.8 to 9.8

4 (21.2)

22

14

22

4030

M6 × 2,

3.4 to 4.9

6 (13 3)

14

8

8

M6 × 2,

M6

3.4 to 4.9

6 (13.3)

14

8

8

P/¨, N/©

M6 × 2

2.94

(*1)

4037

U/T1, V/T2, W/T3

M8

7.8 to 9.8

3 (26.7)

30

14

30

4037

M6 × 2,

3.4 to 4.9

6 (13 3)

14

8

14

M6 × 2,

M6

3.4 to 4.9

6 (13.3)

14

8

14

P/¨, N/©

M6 × 2

2.94

(*1)

4045

U/T1, V/T2, W/T3

M8

7.8 to 9.8

1 (42.4)

60

30

50

4045

M6 × 2,

3.4 to 4.9

6 (13 3)

14

8

14

M6 × 2,

M6

3.4 to 4.9

6 (13.3)

14

8

14

4011 to

4045

A12/r2, A22/t2 (*2)

M4

1.2 to 2.0

14 (2.1)

2

2

2

* 1. Connect using exclusive-use connection bus bar.
* 2. Provided for open chassis type with a minimum capacity of 11 kW. Not provided for external heatsink cooling type.

Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at

an ambient temperature of 30°C (86°F).

2. If ambient temperature exceeds 30°C (86°F), the allowable current of wire may be lowered.
3. Temperature for each wire indicates the maximum allowable conductor temperature.