Yaskawa Varispeed 626M5 User Manual

Page 49

Advertising
background image

3.3 Wiring Main Circuit Terminals

3 -9

2. If ambient temperature exceeds 30°C (86°

F

), the allowable current of wire may be lowered.

3. Temperature for each wire indicates the maximum allowable conductor temperature.

Table 3.3

200 V Class Inverter Power Cable Specifications

Wire Sizes

Model CIMR-

M5

Terminal Symbols

Terminal

Screw

Tighten-

ing

Torque

(N S m)

UL-approved

75°C (167°F)

Temperature-rated

Copper Wire

[AWG (mm

2

)]

600 V Vinyl-

sheath Insulated

Wire (IV, VV)

60°C (140°F)

(mm

2

)

600 V Cross-

linked Polyethy-

lene Wire (IC)

90°C (194°F)

(mm

2

)

600 V Rubber-in-

sulated Cabtyre

Cable (CT)

60°C (140°F)

(mm

2

)

P/¨, N/©

M6

2.94

(*1)

23P7

U/T1, V/T2, W/T3

M5

2.35

8 (8.4)

5.5

3.5

5.5

M5 × 2

2.35

10 (5.3)

3.5

2

3.5

P/¨, N/©

M6

2.94

(*1)

25P5

U/T1, V/T2, W/T3

M5

2.35

8 (8.4)

5.5

3.5

5.5

M5 × 2

2.35

10 (5.3)

3.5

2

3.5

P/¨, N/©

M6

2.94

(*1)

27P5

U/T1, V/T2, W/T3

M5

2.35

8 (8.4)

8

3.5

8

M5 × 2

2.35

8 (8.4)

5.5

3.5

5.5

P/¨, N/©

M6 × 2

2.94

(*1)

2011

U/T1, V/T2, W/T3

M8

6.47

6 (13.3)

14

8

14

M6 × 2

3.4 to 4.9

8 (8.4)

8

5.5

5.5

P/¨, N/©

M6 × 2

2.94

(*1)

2015

U/T1, V/T2, W/T3

M8

6.47

4 (21.2)

22

14

22

M6 × 2

3.4 to 4.9

6 (13.3)

14

8

8

P/¨, N/©

M6 × 2

2.94

(*1)

2018

U/T1, V/T2, W/T3

M8

6.47

3 (26.7)

30

14

30

M6 × 2

3.4 to 4.9

6 (13.3)

14

8

14

P/¨, N/©

M6 × 2

2.94

(*1)

2022

U/T1, V/T2, W/T3

M8

6.47

2 (33.6)

50

22

38

M6 × 2

3.4 to 4.9

6 (13.3)

14

8

14

P/¨, N/©

M6 × 2

2.94

(*1)

2030

U/T1, V/T2, W/T3

M8

7.8 to 9.8

2/0 (67.4)

80

38

80

M6 × 2

3.4 to 4.9

4 (21.2)

22

14

14

P/¨, N/©

M6 × 4

2.94

(*1)

2037

U/T1, V/T2, W/T3

M10

14.7 to

19.6

3/0 (85.0)

100

50

100

2037

M8 × 2,

7.8 to 9.8

3 (26 7)

22

14

22

M8 × 2,

M6

3.4 to 4.9

3 (26.7)

22

14

22

2011 to

2037

A12/r2, A22/t2 (*2)

M4

1.2 to 2.0

14 (2.1)

2

2

2

* 1. Connect using exclusive-use connection bus bar.
* 2. Provided for open chassis type with a minimum capacity of 11 kW. Not provided for external heatsink cooling type.

Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at

an ambient temperature of 30°C (86°

F

).

2. If ambient temperature exceeds 30°C (86°

F

), the allowable current of wire may be lowered.

3. Temperature for each wire indicates the maximum allowable conductor temperature.

3

Advertising