6.5 Speed Control Mode Adjustment Procedure

6-17

Adjustment Item and Procedure

Details

Adjustment completed

NO

YES

NO

NO

YES

YES

NO

YES

Is speedometer

display correct? (See

note.)

Is meter display

greater than motor

speed?

Adjust C1-16 (SM

ADJ

) to

smaller than current value.

Adjust C1-16 (SM

ADJ

) to

greater than current value.

Turn ON and OFF the forward rotation signal

(FWD) to accelerate and decelerate the Motor.

Is load

factor display during

accel/decel correct?

(See note.)

Turn OFF the FWD signal

to stop the Motor.

Display C1-17 data using

the Digital Operator.

Press the DATA/ENTER

Key and the RESET Key at

the same time.

Turn OFF the FWD signal to

stop the Motor.

Is the load factor

display too large?

Adjust C1-17 (LM

ADJ

) to

smaller than current value.

Adjust C1-17 (LM

ADJ

) to

greater than current value.

Press the DSPL Key to

reset the values.

Press the UP Direction Key.

(1)

Speedometer signal adjustment value (C1-16)

(P.U.)

1.5

1.0

0.9

0

0.9 1.0

1.5 (C1−16)

Load factor meter display maximum value (120% of rated torque

for 30 min.)

Speed

ometer

signal

C1-16 = Actual measured motor speed/Speedometer

display value

Example: When motor speed = 6,000 min

−1

and speedometer display

value = 5,940 min

−1

, C1-16 = 6,000/5,940 = 1.01

3.7/2.2

5.5/3.7

7.5/5.5

11/7.5

15/11

202%

178%

164%

176%

164%

LM

18.5/15

22/18.5

30/22

37/30

45/37

148%

143%

164%

148%

146%

LM

Capacity

Capacity

C1-17 = (120% of rated torque for 30 min.)/Load factor meter display

value
Example: When load factor meter display value = 150% at

7.5 kW/5.5 kW, C1-17 = 164/150 = 1.09

Load factor meter display maximum value

Signal output for load factor meter adjustment

0 V

DATA

ENTER

>

RESET

DSPL

Load factor me-

ter signal LM

120% rated torque

for 30 min. signal*

Load factor meter signal adjustment value (C1-17)

(P.U.)

1.5

1.0

0.9

0

0.9 1.0

1.5 (C1−17)

Load

factor

meter

signal

*

When CI-38 bit 7 is ON, a 100% continuous rating signal is output.

Note: Analog monitor signal (speedometer and load factor meter) adjustment is not necessary when using the NC system (M5N).