3 hardware specifications, 4 functional specifications – ProSoft Technology PTQ-104S User Manual

Page 129

Advertising
background image

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Reference

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

9.1.3 Hardware Specifications

Specification

Value

Backplane Current Load

1100 mA maximum @ 5 Vdc ± 5%

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Relative Humidity

5% to 95% (without condensation)

Vibration

Sine vibration 4-100 Hz in each of the 3 orthogonal
axes

Shock

30G, 11 mSec. in each of the 3 orthogonal axes

Dimensions (HxWxD),
Approx.

250 x 40.34 x 103.85 mm
9.84 x 1.59 x 4.09 in

LED Indicators

Module Status
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status

Debug/Configuration Port (Debug)

CFG Port (DEBUG)

DB-9M PC Compatible
RS-232 only
No hardware handshaking

Application Ports

Application Ethernet port RJ45 Connector

Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60
s, applied as specified in section 5.3.2 of IEC 60950:
1991
Ethernet Broadcast Storm Resiliency = less than or
equal to 5000 [ARP] frames-per-second and less than
or equal to 5 minutes duration

9.1.4 Functional Specifications

The PTQ-104S module accepts data read/write commands from a master/client
on the network. In addition, the module can be configured to generate unsolicited
messages in either a spontaneous or cyclic fashion.

The module has 4000 words of user defined internal register space that are
accessible to the protocol driver and to the Quantum processor memory. Any of
the supported database types can be individually located (within the total
database size limit of 4000 words) and each database point is mapped within the
module and can be assigned to one or more Groups. The supported database
point types are:

Database Type

Description

Event Generation Point Size

M_SP_NA

Monitored single-point database

State Change

1 bit

M_DP_NA

Monitored dual-point database

State Change

2 bits

M_ST_NA

Monitored step-point database

State Change

1 byte

M_ME_NA

Monitored normalized-point database

Dead-band

1 word

M_ME_NB

Monitored scaled-point database

Dead-band

1 word

M_ME_NC

Monitored short-float point database

Deadband

2 words

M_IT_NA

Monitored integrated total database

N/A

2 words

C_SC_NA

Command single-point database

N/A

1 bit

ProSoft Technology, Inc.

Page 129 of 201

March 4, 2013

Advertising