It would imply that the parameter points would be configured as follows:

M_ME_NA

Monitored Measured Normalized Point

Associated Parameter Point

400

2400

401

2401

402

2402

403

2403

...

...

409

2409

In order to send a change of deadband for M_ME_NA Point 400, the Client would
send a command type 110 to point 2400.

M_ME_NB

Monitored Measured Normalized Point

Associated Parameter Point

500

2500

501

2501

502

2502

503

2503

...

...

509

2509

In order to send a change of deadband for M_ME_NB Point 500, the Client would
send a command type 110 to point 2500.