M_me_na, M_me_nb – ProSoft Technology PTQ-104S User Manual
Page 165
Advertising

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Reference
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
400
2400
401
2401
402
2402
403
2403
...
...
409
2409
In order to send a change of deadband for M_ME_NA Point 400, the Client would
send a command type 110 to point 2400.
M_ME_NB
Monitored Measured Normalized Point
Associated Parameter Point
500
2500
501
2501
502
2502
503
2503
...
...
509
2509
In order to send a change of deadband for M_ME_NB Point 500, the Client would
send a command type 110 to point 2500.
ProSoft Technology, Inc.
Page 165 of 201
March 4, 2013