ProSoft Technology PTQ-104S User Manual

Page 57

Advertising
background image

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Module Configuration

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

The first command states:

Field

Value

Meaning

Command Type

1

The type of operation to perform
1 = Read data from the Quantum into the PTQ

PTQ Address

0

The destination address within the PTQ

Point Type

4

The range of registers to read from the Quantum
4 = 4:x style register

Quantum Address

1

The starting address of the data within the Quantum
This would be Point Type + offset
Example: 40000 + 1 = 40001

Word Count

100

The number of registers to transfer

The second command states:

Field

Value

Meaning

Command Type

1

The type of operation to perform
1 = Read data from the Quantum into the PTQ

PTQ Address

100

The destination address within the PTQ

Point Type

4

The range of registers to read from the Quantum
4 = 4:x style register

Quantum Address

104

The starting address of the data within the Quantum
This would be Point Type + Quantum Address
Example: 40000 + 104 = 40104

Word Count

107

The number of registers to transfer

The following diagram shows the result of this example.

Quantum Memory Address

PTQ Memory Address

40001

0

40010

First Command

9

40020

19

40030

29

40040

39

40060

59

40070

69

40080

79

40090

89

40100

99

40104

100

40111

Second Command

110

40200

199

40207

206

ProSoft Technology, Inc.

Page 57 of 201

March 4, 2013