3 use daylight savings time, 4 database register, 6 [iec-870-5-104 – ProSoft Technology PTQ-104S User Manual

Page 76: Iec-870-5-104

Advertising
background image

Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

5.5.3 Use Daylight Savings Time

Yes or No

This parameter specifies if daylight savings time will be used in the time
computation.

5.5.4 Database Register

-1 or 0 to 3992 as an even value

This parameter specifies if the NTP time computed by the driver is to be placed
into the module’s database. If a value of -1 is specified, the time will not be
placed into the database. If the value is between 0 and 3992, the time will be
placed in the database. The first 4 bytes will represent the seconds since
1/1/1970, and the second 4 bytes will represent the number of microseconds. An
even value should be used for the register value in order for the data to be stored
correctly.

5.6

[IEC-870-5-104]

This section provides information required to configure a server application with
the module. An item of concern is the maximum size of the total database.
Although it is possible to configure a database of considerable size, the
maximum Class 0 request may not exceed 2048 bytes in size.

Page 76 of 201

ProSoft Technology, Inc.

March 4, 2013

Advertising