Block format for read – ProSoft Technology PTQ-104S User Manual

Page 70

Advertising
background image

Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

Block Format for Read

Word Offset in Block

Data Field(s)

Description

0

Done Flag

The word will be set to 0 when the command is
complete.

1

Block ID

This word will contain the value of 9250

2

Scan Count

This status value contains a counter incremented
on each scan of the module's main loop.

3 to 4

Product Name

This two-word data area contains the text values
representing the product name.

5 to 6

Revision

This two-word data area contains the text values
for the revision number.

7 to 8

Op Sys #

This two-word data area contains the text values
for the operating system number.

9 to 10

Run Number

This two-word data area contains the text values
for the run number.

11

Number of block
reads

This data area contains the total number of block
read errors.

12

Number of block
writes

This word contains the total number of block write
errors.

13

Number of blocks
parsed

This word contains the total number of write
blocks successfully parsed.

14

Number of block
transfer errors

This word contains the total number of block
transfer errors.

15

t0 Timeout

Number of t0 errors recognized by the module

16

t1 Timeout

Number of t1 errors recognized by the module

17

t2 Timeout

Number of t2 errors recognized by the module

18

t3 Timeout

Number of t3 errors recognized by the module

19

Receive Sequence

This word contains the current Receive Sequence
number (NR) sent by the module. This value is a
part of every message sent to the client unit.

20

Bad Address

This word contains the number of messages
received with a wrong Common ASDU Address
value

21

Bad Length

This word contains the number of messages
received by the host that does not contain a valid
length field

22

Rx Count

Number of messages sent

23

Tx Count

Number of messages received

24

Socket State

This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for Connection
1 = Transmit Message if Ready
2 = Receive Packet and process message
3 = Process multiple messages in packet
50 = Send TestFR ACT
51 = Wait for TestFR Con
60 = Send S-Format Message
1000 = Close Socket
1001 = Wait for Socket to Close

25

Socket Open Count

This word contains the number of times the socket
listen function was executed

Page 70 of 201

ProSoft Technology, Inc.

March 4, 2013

Advertising