This section takes the following parameters:
 Point #
 DB Address
 Groups
 Default Deadband
 IV DB Bit
Each point is one word and the DB Address value corresponds to the word offset
in the database.

The Database Address value should be located in a database area that is
constantly being moved from the Quantum processor to the PTQ-104S module.
Therefore, this value should be configured in an area that is used on a Backplane
Command Function 1.

Refer to the Group Codes (page 98) section for a listing of Group Codes.

5.17 [M_IT_NA_1 104]

This section defines the monitored integrated totals (counter) database. This
information is sourced from the database and is transferred to the remote Client
unit.

This section takes the following parameters:
 Point #
 DB Address
 Group(s)
 IV DB Bit
Each point is two 16-bit words and the DB Address value corresponds to the
double-word offset in the module memory database. For additional information
on how to set these parameters, see the Reference chapter of this manual.

5.18 [C_SC_NA_1 104]

This section defines the single point command database. This information is
sourced from the remote Client and is transferred to the database. You can
associate a command with a monitored single-point database value to coordinate
the command/monitor operation. You must enter the correct Monitor Point # and
Monitor DB Address values in the table. If the Require Select parameter is not
set to zero, a select command must be received before an execute command will
be processed.

This section takes the following parameters:
 Point #
 DB Address
 Monitor Point #
 Monitor DB Address
 Require Select
Each point is one bit and the DB Address value corresponds to the bit offset in
the module memory database. For additional information on how to set these
parameters, see the Reference chapter of this manual.